| F07 | DC/DC_Softsart_Fault | - Startup problems, replace the control board, if not, remove the motherboard to measure the MOS tube is in good condition.
|
| F10 | AuxPowerBoard_Failure | - Power supply failure, update power board.
|
| F13 | Working mode change | Inverter work mode changed:- Reset the inverter.
- Seek help from Sunsynk.
|
| F15 | Short circuit protecting | Short circuit fault:- Maintain the connection.
- Proceed to the settings to modify the work mode.
- Wait approximately 3-4 minutes.
- The device should return to its normal working condition, with the error cleared.
- Seek help from Sunsynk.
|
| F18 | AC over current fault or hardware | AC slide over current fault:- Check if the backup load power is within the range of the inverter.
- Restart and check if it is normal.
|
| F20 | DC over current fault of the hardware | DC over current fault:- Check PV module and battery connections.
- Reset the system.
|
| F23 | AC leakage current is trans over current | Leakage current fault:- Check the PV module and inverter cables.
- You may have a faulty PV panel (earth short).
- Restart inverter.
|
| F24 | DC insulation impedance failure | PV isolation resistance is too low:- Check if the connection of PV panels and inverter are firmly connected.
- Check if the earth bond cable on inverters is connected to the ground.
|
| F26 | The bus bar is unbalanced | - Please wait 5 minutes to see if it returns to normal.
- Fully reset the inverter.
|
| F29 | ECAN communicate | - When in parallel mode, check the parallel communication cable connection and hybrid communication address settings.
- During the parallel system startup period, inverters will report F29. When all inverters are in ON status, it will disappear automatically;
- If the fault exists, please contact us for help.
|
| F30 | Load current exceeding | - Try tu reduce the load power.
- Seek help from Sunsynk.
|
| F34 | Over Load Protection | - Reduce appliance power on LOAD side (system will auto-reboot in 2 minutes).
|
| F35 | No AC grid | - Check if the inverter’s connected to the AC grid.
- Check if the RSCD had not tripped.
- Check if the switch and fuses between the inverter and grid are all switched on.
|
| F37 | Battery activation overcurrent | - System will auto-reboot in 2 minutes.
|
| F39 | DC-DC over current | - Push the power button of the inverter to restart it, system will auto-reboot in 2 minutes.
|
| F40 | DC over current | - If the battery SOC shows 0, turn off the unit and restart it
|
| F41 | Parallel system stop | - Check the hybrid inverter working status. If there’s 1pcs hybrid inverter is in OFF status, the other hybrid inverters may report F41 fault in parallel system.
- If the fault exists, please contact us for help.
|
| F42 | AC line low voltage | Grid voltage fault:- Check if the voltage is in the range of standard voltage in specification, this can be adjusted via the grid set up page.
- Check if grid cables are correctly connected.
|
| F45 | AC line HIGH voltage | - Grid exceeds 251V, and the inverter switch is off
- Grid exceeds 251V, and the inverter switch is on, but the battery is drained
|
| F47 | AC over frequency | Grid voltage fault:- Check if the voltage is in the range of standard voltage in specification, this can be adjusted via the grid set up page.
- Check if grid cables are correctly connected.
|
| F48 | AC lower frequency | Grid frequency out of range:- Check if the frequency is in the range of specification.
- You may need to adjust the frequency on the grid set up page.
|
| F55 | DC busbar voltage is high | User: External Battery Input voltage is high- Installer: check inverter’s bus voltage might be too high. Observe the battery voltage value on the LCD (the value will be restored automatically if it is normal), if it is not normal for a long period, you have to check the control board or the voltage acquisition part of the motherboard.
|
| F56 | DC bus bar voltage is too low | Battery low voltage:- Check if the battery voltage is too low.
- If the battery voltage is too low use the PV or grid to charge the battery.
- Check the battery BMS.
Important: Especially with lithium batteries, ensure that the batteries Max. discharge current or power specification is the same or higher than the inverter specification. |
| F60 | Smoke alarm | When the smoke alarm is lifted, use the App to restart the inverter (Refer to the relevant content of the App user manual). |
| F61 | Bus one shutdown | - Reset the inverter.
- Seek help from Sunsynk.
|
| F62 | DRMs0 stop | Reserved Error code |
| F63 | FAN Error | - A technician needs to check the internal fan wire or replace fan.
- Seek help from Sunsynk.
|
| F64 | Heat sink high-temperature failure | Heat sink temperature is too high:- Check if the working environment temperature is too high.
- Turn off the inverter for 30 minutes and restart.
|